Scroll To Top

P7341M-MP-GC-15000V-XLP-PVC

Home   »   P7341M-MP-GC-15000V-XLP-PVC   »   P7341M-MP-GC-15000V-XLP-PVC
P7341M-SHD-GC

P7341M-MP-GC-15000V-XLP-PVC

Insulation

XLP

Sizes

4 -2 AWG UL 1072, ASTM B 8, ICEA S-75-381/NEMA WC58

Share it

MINE POWER FEEDER CABLE
XLP / PVC 90˚C MSHA
15000V MINING GRADE

  • UL, CSA, MSHA
  • ROHS compliant – Restriction of use of Hazardous Substances
  • NEC Article 400 permitted use for specific applications.
  • NFPA 70 permitted use in Hazardous Locations Classes I, II, III, Divisions 1 & 2 as outlined in Articles 501, 502, 503 section 140.
  • Offered in European Harmonized BBJ dual rating as SOOW/H07
  • Meets UL’s VW-1, CSA’s FT-2 and MSHA’s flame test requirements
  •  Listed for Outdoor Use as well as Continuous Submersion in Water.

Conductors:

Bare copper, concentric strand ASTM B 8.

Conductor Shield:

Extruded semi-conducting compound. Insulation: Cross-linked polyethylene (XLP) 90ºC.

Insulation Shield:

Extruded semi-conducting compound, copper tape 0.003.

Grounding Conductors:

Bare copper Class B.

Ground Check:

Bare copper, ICEA S-75-381 sec 4.6; Yellow XLP 45mils insulation.

Cable Assembly:

Three power conductor, ground check and two non-insulated grounding conductors cabled together with rubber fillers to form round core; Estrofol binder tape applied overall.

Reinforcement:

Reinforcement applied over the assembly for mechanical strength. Jacket: Black flame retardant PVC, ICEA S-75-381 table 4-7.

Color Code:

Color code tape: black, white, red applied under metallic shielding tape provides circuit identification, ICEA S-75-381 sec 4.6.

MSHA:

P-7K-254064-1

CSA:

CSA certified product available.