TYPE DLO/RHH/RHW-2/RW90
EXTRA FLEXIBLE
SINGLE CONDUCTOR
CABLE 600/2000 VOLTS
Nominal Voltage:
RHH/RHW-2 600 and 2000V, R90 CSA, RW90 C9UL), 1kV, DLO 2kV.
Conductors:
Annealed flexible stranded tin coated copper conductor in accordance with ASTM B-172, ASTM B-33.
Cable Reinforcement:
Power conductors and cured rubber fillers cabled together. Single faced rubber filled binder tape applied over the assembly for mechanical protection.
Separator:
A suitable tape separator between the conductor and insulation.
Insulation:
Ethylene-propylene rubber (EPR) type EP, meeting UL, CSA and ICEA requirements for 90˚C
Jacket:
A heavy duty, thermosetting CPE or CP compound in accordance with ICEA S-68-516 NEMA WC-8.
Color of Jacket:
Black; Other colors available
MSHA:
P-7268080-01-MSHA (CPE)
UL:
E193954 (CPE Jacket) RHW-2 90˚C Wet and Dry, VW-1, Sun Res, for 1/0 and larger ST-1, FT-4, IEEE1202, for CT use.
C(UL): E19354:
“(TYPE) RW90 EP”; “1000V”; “FT1”
CSA: 1101209 (LL103932):
“205591” or “103932”; RW-90 90˚C; “FT1”; “FT4”; “-40˚C”; “OIL RES” (CPE) TC (Tray Cable) SR (Sun Res) 1/0 and larger