Construction
Conductors:
Flexible strand tinned copper conductor, ASTM B-172 and ICEA S-75-381, table 3-22.
Seperator:
Polyester tape between conductor and insulation. ICEA S-75-381.
Conductor Shield:
Extruded semi-conducting layer over conductor. ICEA S-75-381 sec. 3.14
Insulation:
Ethylene-propylene rubber (EPR) ICEA S-75- 381, table 3-22.
Insulation Shield:
Semi-conducting bedding tape and composite tinned copper/polyamide braid 60% minimum coverage.
Color Code:
Polyamide braid color code - black, white, red, ICEA S-75-381.
Grounding Conductors:
Tinned copper - ICEA S-75-381 Tab. 3-22.
Ground Check:
Yellow polypropylene-insulated tinned copper conductor, ICEA S-75-381 Tab. 3-22.
Cable Assembly:
Three power conductors, ground check and two non-insulated grounding conductors cabled together to form a round cable core.
Separator:
Single faced rubber-filled binder tape applied over core.
Jacket: