TYPE UF / NMC-B CABLE,
600 VOLT, 2 AND 3 CONDUCTOR
WITH OR WITHOUT GROUND
Conductors: (for Multi-conductor cables only):
Sizes 14, 12, & 10 AWG: Solid, annealed bare copper per ASTM B-3, UL-493 and UL-719.
Sizes 8 & 6 AWG:Concentric, compressed stranded (Class B).
Conductors: (for Single Conductor cable only)
Sizes 14, 12, 10 & 8 AWG: Solid, annealed bare copper per ASTM B-3, UL-493.
Sizes 6 to 4/0 AWG: Concentric, compressed stranded (Class B) ASTM B-3, UL-493.
Insulation: For Multi-conductor cable only: Polyvinyl Chloride (PVC). Ul-493 and UL-719.
Ground Wire: For 2 or 3 conductor cable with ground. Solid, annealed bare copper per ASTM B-3.
Cable Assembly: Multi-conductor cables are assembled flat parallel. For cables with ground, the ground wire is placed between two of the insulated conductors.
Overall Jacket: (integral jacket and insulation for single conductor cable) Sunlight, moisture and
fungusresistant. Gray PVC UL-493 and UL- 719.
Color Code: Two-conductor cable: Black, White Three conductor cable: Black, White, Red.
Direct Burial Underground feeder cable with or without ground and a sunlight-resistant PVC overall jacket.
UL Listed and OSHA acceptable. In accordance with Articles 336 and 339 of the National Electrical Code (and subject to local code requirements), Type UF cables may be used for underground feeder or branchcircuit wiring for installation above or below ground, including direct burial, and in wet or corrosive locations. Multi-conductor Type UF (Type NMC-B) cables may also be used for exposed or concealed interior wiring in wet, dry or corrosive locations and in cable trays.