Conductor: Annealed extra flexible stranded bare copper in accordance with ASTM B-172 and ICEA S-75-381.
Separator: A suitable tape separator between the conductor and insulation.
Insulation: Ethylene-propylene rubber (EPR) type EP.
Cable Reinforcement: single faced rubber filled binder tape over insulation.
Jacket: CPE thermosetting compound, heavy or extra heavy duty in accordance with par. 3.21 of ICEA S-75-381; Neoprene optional jacket available.
Color Code: Black
Cable Identification: Indent print on jacket. (Size) AWG (no.)/Type
W Portable Power Cable 90°C 2000V (UL) P-MSHA.
Approvals:
UL: E207132
MSHA: P-7K-26801 (CPE);
P-7K-268077 (NEOPRENE)
C(UL): E207132
CSA: 1523058,
Paige Part # |
Power Conductor Size |
Power Conductor Stranding |
Nominal Insulation Thickness |
Nominal O.D. |
Approx. Weight |
Ampacity (1) 40ºC Ambient Temp. |
|
|
|
Inches |
mm |
Inches |
mm |
Ibs/1000 ft |
kgs/km |
|
1100014 |
8 |
162/30 |
0.060 |
1.52 |
0.441 |
11.2 |
145 |
216 |
81 |
1100002 |
6 |
264/30 |
0.060 |
1.52 |
0.511 |
12.9 |
200 |
298 |
104 |
1100003 |
4 |
418/30 |
0.060 |
1.52 |
0.564 |
14.3 |
255 |
379 |
141 |
1100004 |
2 |
660/30 |
0.060 |
1.52 |
0.651 |
16.5 |
375 |
558 |
192 |
1100015 |
1 |
836/30 |
0.080 |
2.03 |
0.729 |
18.5 |
475 |
707 |
221 |
1100006 |
1/0 |
1056/30 |
0.080 |
2.03 |
0.751 |
19.0 |
530 |
789 |
261 |
1100007 |
2/0 |
1320/30 |
0.080 |
2.03 |
0.800 |
20.3 |
650 |
967 |
300 |
1100008 |
3/0 |
1672/30 |
0.080 |
2.03 |
0.856 |
21.7 |
750 |
1116 |
351 |
1100009 |
4/0 |
2090/30 |
0.080 |
2.03 |
0.981 |
24.9 |
970 |
1444 |
405 |
1100010 |
250 MCM |
2496/30 |
0.095 |
2.41 |
1.001 |
25.4 |
1130 |
1682 |
455 |
1100020 |
350 MCM |
888 37 x 24 |
0.095 |
2.41 |
1.146 |
29.1 |
1444 |
2149 |
552 |
1100030 |
500 MCM |
1221 37 x 33 |
0.095 |
2.41 |
1.255 |
31.9 |
1913 |
2847 |
695 |
*Ampacities (Amps per conductor) are based on 90˚C conductor temperature. |