Conductor: Class C (19 strand).
Insulation: (XLPE) Heat and moisture resistant, thermosetting cross-linked polyethylene meeting the requirements of ICEA S-95-658 (NEMA WC 70). Acceptable 90ºC Wet and Dry.
Jacket: Heat and moisture resistant, black, PVC meeting requirements of ICEA S-95-658 (NEMA WC 70).
Assembly: The insulated circuit conductors are laid flat and parallel together. The jacket will be applied directly over the insulated conductors encapsulating them.
Color Code: Black, Yellow, Red.
Marking: The overall jacket will have either of the following information printed:
“Paige PUMPWIRE P7370-SP Submersible Pump Cable 3 x ##AWG XLPE/PVC 90C 1000V”.,
Physical:
PAIGE PART # |
NUMBER OF CONDUCTORS |
CONDUCTOR SIZE |
INSULATION THICKNESS XLPE |
JACKET THICKNESS |
NOMINAL CABLE O.D. |
CABLE WEIGHT (LB/MFT*) |
|
|
(AWG) |
(MIL) |
(MIL) |
INCHES |
MM |
|
020041 1KV |
3 |
8 |
55 |
45 |
0.910 x 0.370 |
23.114 x 9.398 |
289 |
020051 1KV |
3 |
6 |
55 |
45 |
1.025 x 0.405 |
26.035 x 10.287 |
405 |
020061 1KV |
3 |
4 |
55 |
45 |
1.175 x 0.455 |
29.845 x 11.557 |
585 |
020071 1KV |
3 |
2 |
55 |
45 |
1.360 x 0.520 |
34.544 x 13.208 |
860 |