Portable Extra Flexible EPR/CPE Submersible Pump Cable
TWISTED UNJACKETED RUBBER INTERNATIONAL STYLE SUBMERSIBLE PUMP CABLE
3 CONDUCTOR W/GROUND
USE/RHW 12 AWG AND LARGER
RHW twisted insulated with EPR and Jacketed with CPE, submersible and direct burial rated at 1000V.
This specification covers the construction requirements for submersible pump cable rated at 1000 volts at operating temperatures up to 90°C. Individual conductors are insulated with “RHW” rubber and jacketed with colored CPE, and then twisted together. This cable is also suitable for direct burial UL labeled.
2 & 3 CONDUCTORS – WITHOUT GROUND
Paige Part # | Size | Power Conduc- tor Stranding | Nominal Thickness of Insulation | Nominal Thickness of Jacket | Approx. Diameter After Jacket | Approx. Diameter AfterTwisted | Approz. Weight |
---|---|---|---|---|---|---|---|
064X25MM | 4 x 25mm | 180 x 0.4 | 1.52mm | 0.76mm | 11.1mm | 26.9mm | 1192kg/km |
064X35MM | 4 x 35mm | 254 x 0.4 | 1.52mm | 0.76mm | 11.8mm | 28.6mm | 1550kg/km |
064X50MM | 4 x 50mm | 384 x 0.4 | 2.03mm | 1.14mm | 15.5mm | 37.5mm | 2360kg/km |
064X70MM | 4 x 70mm | 514 x 0.4 | 2.03mm | 1.14mm | 17.3mm | 41.9mm | 3160kg/km |
064X95MM | 4 x 95mm | 684 x 0.4 | 2.03mm | 1.14mm | 19.4mm | 47.0mm | 4037kg/km |
064X120MM | 4 x 120mm | 870 x 0.4 | 2.28mm | 1.65mm | 22.1mm | 53.5mm | 5274kg/km |
064X240MM | 4 x 240mm | 1752 x 0.4 | 2.28mm | 1.65mm | 27.7mm | 67.1mm | 9668kg/km |
2 & 3 CONDUCTORS – WITH GROUND
Conductors: Annealed flexible stranded bare copper to IEC 60 228.
Insulation: UL RHW, 90° C, rubber, conforming to UL standard 44.
Jacket: UL heavy duty CPE, colored, conforming to UL standard 44. Optional jacket also available in CFPE Hypalon and Neoprene.
Color Code: Jacket colored as follows:
4/C cables: BLACK/YELLOW/RED/GREEN
Assembly: Four jacketed conductors are twisted together in a suitable lay.
Marking: Ink print jacket surface: “Size AWG Type USE or Type RHW 1000 Volts Paige Electric Corp. (UL) Submersible Pump Cable.
Testing: Physical and Electrical tests in accordance with the requirements of Underwriters’ Laboratories standards 44 for Type USE/RHW Submersible Pump Cables.
“Made exclusively for Paige Electric Company and subject to Paige’s high quality standards by Telefonika Cable: Krakow, Poland 30-663 Krakow ul. Wielicka 114″.