Scroll To Top

15000V SP cable – P7376-SP-15kV

Home   »   15000V SP cable – P7376-SP-15kV   »   15000V SP cable – P7376-SP-15kV

15000V SP cable – P7376-SP-15kV

Voltage

15000V

Insulation

EPR - Ethylene Propylene Rubber

Sizes

2 AWG - 1000 MCM

Jacket

PVC - Polyvinyl Chloride

Temp Dry/Wet

105°C Dry, 105°C Wet

Share it
Approvals

15KV – SUBMERSIBLE PUMP
SHIELDED POWER CABLE
TYPE MV-105
3 CONDUCTORS WITH GROUND

Shielded, Medium Voltage and UL listed wet and dry locations. Suitable for use as a submersible cable. Direct Burial rated.

Shielded, Medium Voltage and UL listed wet and dry locations. Suitable for use as a submersible cable. Direct Burial rated.

Conductors: Consist of uncoated soft, copper strands meeting the requirements of ASTM B3. Conductor shall be supplied as Class B compact per ASTM B496.

Conductor Shield: Consists of an extruded semiconducting layer.

Insulation: The insulation is ethylene-propylene rubber (EPR) extruded in a single pass with the conductor and insulation shields to the wall thickness.

Insulation Shielding: Consist of a semi-conducting extruded compound and a 5 mil bare copper metallic tape shield overlapped a minimum of 20%.

Conductor Coding: Phase identification for multiconductor cables is provided by a colored stripe on the insulation shield of each of the conductors (red, black, blue).

Ground: Standard multi-conductor cables include one stranded bare copper ground in one of the outer cable interstices. The ground wire is sized per UL requirements. Custom ground wire sizes and configurations are available upon request.

Assembly: Conductors and ground wire are cabled together with a left hand lay and suitable fillers are used in the interstices to round out the cable cross section. A mylar binder tape is applied overall.

Jacket: A sunlight and ozone resistant jacket of polyvinyl chloride (PVC) or chlorinated polyethylene (CPE) is extruded over the single and multiconductor assembly.

  • Conforms to ICEA S-93-639/NEMA WC74 and AEIC CS8 for Extruded Dielectric Shielded Power Cable 5-46KV.
  • Cable listed by UL as Type MV-105 or MC per Standard 1072.
  • Listed by UL as Sunlight Resistant, for Direct Burial and For CT Use.
  • Listed by CSA as Type Power Cable per Standard SCA C68.3 (with -40˚C PVC jacket).